1.:

Bulletin 140UE L-Frame

 

Breaker Frames

Rated
Current
I
n [A]

Breaking Capacity (50 Hz)
I
cu /Ics [kA]

Cat. No.

220…240V

380…415V

3-Pole

4-Pole

630

65

65

35

35

140UE-L3X3

140UE-L3X4

85

85

50

50

140UE-L5X3

140UE-L5X4

100

100

70

70

140UE-L7X3

140UE-L7X4

Trip Units, Thermal-Magnetic

Rated Current In [A]

Adjustment

Range [A]

Protection Type

Cat. No.

Thermal Trip
I
r =(0.8… 1.0) In (Adjus.)

Magnetic Trip
I
m = 5… 10 x In

3-Pole

4-Pole

250

200…250

1250…2500

AA

140UE-LTF3-D25

140UE-LTF4-D25

320

256…320

1600…3200

AA

140UE-LTF3-D32

140UE-LTF4-D32

400

320…400

2000…4000

AA

140UE-LTF3-D40

140UE-LTF4-D40

500

400…500

2500…5000

AA

140UE-LTF3-D50

140UE-LTF4-D50

630

504…630

3150…6300

AA

140UE-LTF3-D63

140UE-LTF4-D63

Trip Units, Electronic

Rated Current In [A]

Adjustment Range [A]

Protection Type

Cat. No.

Thermal Trip ‡ 
I
r = 0.4…1.0 x In

Magnetic Trip
I
m = 2…10 x In

3-Pole

4-Pole

630

250…630

1260…6300

250…630 A LS Electronic Trip Unit

140UE-LTL3-D63

140UE-LTL4-D63

630

250…630

1260…6300

250…630 A LSI Electronic Trip Unit

140UE-LTH3-D63

140UE-LTH4-D63

630

250…630

1260…6300

250…630 A LSG Electronic Trip Unit

140UE-LTG3-D63

140UE-LTG4-D63

630

250…630

1260…6300

250…630 A LSIG Electronic Trip Unit

140UE-LTI3-D63

140UE-LTI4-D63

Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Current In [A]

Protection Type
I
n

Breaking Capacity 380…415V (50 Hz)

3 Poles

35 kA

50 kA

70 kA

Cat. No.

Cat. No.

Cat. No.

250

AA

140UE-L3F3-D25

140UE-L5F3-D25

140UE-L7F3-D25

320

AA

140UE-L3F3-D32

140UE-L5F3-D32

140UE-L7F3-D32

400

AA

140UE-L3F3-D40

140UE-L5F3-D40

140UE-L7F3-D40

500

AA

140UE-L3F3-D50

140UE-L5F3-D50

140UE-L7F3-D50

630

AA

140UE-L3F3-D63

140UE-L5F3-D63

140UE-L7F3-D63

 

Rated Current In [A]

Protection Type
I
n

Breaking Capacity 380…415V (50 Hz)

4 Poles

35 kA

50 kA

70 kA

Cat. No.

Cat. No.

Cat. No.

250

AA

140UE-L3F4-D25

140UE-L5F4-D25

140UE-L7F4-D25

320

AA

140UE-L3F4-D32

140UE-L5F4-D32

140UE-L7F4-D32

400

AA

140UE-L3F4-D40

140UE-L5F4-D40

140UE-L7F4-D40

500

AA

140UE-L3F4-D50

140UE-L5F4-D50

140UE-L7F4-D50

630

AA

140UE-L3F4-D63

140UE-L5F4-D63

140UE-L7F4-D63

 Assembled Circuit Breakers, Electronic Trip Units

Rated Current In [A]

Protection Type

Breaking Capacity 380…415V (50 Hz)

3 Poles

35 kA

50 kA

70 kA

Cat. No.

Cat. No.

Cat. No.

630

250…630 A LS Electronic Trip Unit

140UE-L3L3-D63

140UE-L5L3-D63

140UE-L7L3-D63

630

250…630 A LSI Electronic Trip Unit

140UE-L3H3-D63

140UE-L5H3-D63

140UE-L7H3-D63

630

250…630 A LSG Electronic Trip Unit

140UE-L3G3-D63

140UE-L5G3-D63

140UE-L7G3-D63

630

250…630 A LSIG Electronic Trip Unit

140UE-L3I3-D63

140UE-L5I3-D63

140UE-L7I3-D63

 

Rated Current In [A]

Protection Type

Breaking Capacity 380…415V (50 Hz)

4 Poles

35 kA

50 kA

70 kA

Cat. No.

Cat. No.

Cat. No.

630

250…630 A LS Electronic Trip Unit

140UE-L3L4-D63

140UE-L5L4-D63

140UE-L7L4-D63

630

250…630 A LSI Electronic Trip Unit

140UE-L3H4-D63

140UE-L5H4-D63

140UE-L7H4-D63

630

250…630 A LSG Electronic Trip Unit

140UE-L3G4-D63

140UE-L5G4-D63

140UE-L7G4-D63

630

250…630 A LSIG Electronic Trip Unit

140UE-L3I4-D63

140UE-L5I4-D63

140UE-L7I4-D63

 
Isolation Disconnector — IEC 60947-3

Rated Current
I
n [A]

Thermal Trip
I
r = In [A]

Magnetic Trip [A]
I
m = 10 x In

Breaking Capacity

(50 Hz)
I
cu /Ics [kA]

Cat. No.

220… 240V

380… 415V

3-Pole

4-Pole

630

6300

100

100

70

70

140UE-L7S3-D63

140UE-L7S4-D63

Earth Leakage Protector

Earth Leakage Adjustment Range [A]

Max. Current [A]

Cat. No.

3-Pole

4-Pole

0.3…10

400

140U-L-ELP4003

140U-L-ELP4004

630

140U-L-ELP6303

140U-L-ELP6304

 Internal Control Modules — Field Installed

 

Description

Mounting location

Cat. No.

Click to enlarge - 140U-43-1

Auxiliary Contact (AX)
Electrically indicates “ON/OFF” status of breakers

(1) 1a-1b

Click to enlarge - 140U-51-2

140U-H-EA1

(2) 1a-1b

Left AND Right Side

140U-H-EA2

Alarm Contact (AL)
Electronically indicates when the breaker is in the “TRIPPED” state

(1) 1M (make)-1B (break)

Click to enlarge - 140U-43-2

140U-J-ER1

Right Side ONLY

Click to enlarge - 140U-43-6

Auxiliary/Alarm Contact (AX/AL)
Combination

Combination of auxiliary contact and alarm contact

(1) 1a-1b
(1) 1M (make)-1B (break)

Click to enlarge - 140U-43-2

140U-J-EA1R1

Right Side ONLY

Click to enlarge - 140U-43-9

Shunt Trip (SNT)
Provides remote tripping of the circuit breaker
Undervoltage trip not available when shunt trip is used

24…60 V, 50/60/DC

Click to enlarge - 140U-43-10

140U-H-SNJ

110…240V; 50/60 Hz

140U-H-SND

110…125V DC

140U-H-SNZD

380…440V AC, 220…250V DC

140U-H-SNN

380…600V, 50/60 Hz

Left Side ONLY

140U-H-SNB

Undervoltage Release (UVT)
Automatically trips breaker when voltage falls between preset value, 35…70%
Shunt trip is not available when undervoltage release is used

24V, 50/60Hz AC; 24V DC

Click to enlarge - 140U-43-10

140U-H-UJ

110…127V, 50/60 Hz

140U-H-UD

208…240V, 50/60 Hz

140U-H-UA

380…500V, 50/60 Hz

Left Side Only

140U-H-UB

External Accessories

 

Description

Cat. No.

Click to enlarge - 140U-L-TS_r_bw

Terminal Shields
IP20 Ingress Protection Rating

Qty: 1

140U-L-TS

Terminal Shield, 4-Pole

Qty: 1

140U-L-TS4

Click to enlarge - 140_BASE_R-bw

Plug-in Adapter, 3-Pole

Qty: 1

140U-L-PAD3

Plug-in Adapter, 4-Pole

Qty: 1

140U-L-PAD4

Plug-in adapter auxiliary contact

Qty: 1

140U-L-PDK

Click to enlarge - ab_switch-21474_bw

Motor Operator
Remotely opens, closes, and resets the circuit breaker
120…240V AC; 125V DC

Qty: 1

140U-L-EOPD

Motor Operator
Remotely opens, closes, and resets the circuit breaker
24V DC

Qty: 1

140U-L-EOPZ

Click to enlarge - interlock 2 bw-21996

Sliding Bar Interlock

Qty: 1

140U-L-SBLK

Click to enlarge - 140U-52-3

Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
Type 1/3R/12/4/4X
Flange-Mount Operating Handle
Non-Metallic

4 ft (1.2 m) Cable

140U-L-FCX04

6 ft (1.9 m) Cable

140U-L-FCX06

10 ft (3.0 m) Cable

140U-L-FCX10

Click to enlarge - 140M-21-2

Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
Type 1/3R/12/4/4X
Flange-Mount Operating Handle
Stainless Steel

4 ft (1.2 m) Cable

140U-L-FCS04

6 ft (1.9 m) Cable

140U-L-FCS06

10 ft (3.0 m) Cable

140U-L-FCS10

Click to enlarge - lockout lrg_bw

Rotary, Variable-Depth Operating Mechanism
UL Type 3/12/4/4X, IP 66 Rotary handle
12 in. (30.48 cm) operating rod

Black Handle

140U-L-RVM12B

Red/Yellow Handle

140U-L-RVM12R

Rotary, Variable-Depth Operating Mechanism
UL Type 3/12/4/4X, IP 66 Rotary handle
21 in. (53.34 cm) operating rod

Black Handle

140U-L-RVM21B

Red/Yellow Handle

140U-L-RVM21R

Click to enlarge - 140M-20-4

End Cap Kit
Provides 3-phase connections for terminal or bolt-on connections
Metric hardware provided

Qty: 1

140U-L-ECM

End Cap Kit, 4-Pole – Metric Hardware (1)

Qty: 1

140U-L-ECM4

Click to enlarge - 140U-L-MHM

Replacement Mounting Hardware
(4) M5 – 0.8 x 100 mm

Qty: 1

140U-L-MHM

Optional Terminal Lug Kits

 

Description

Terminal Body Material

Wire Type

Wire Size, AWG

Wire Size, Metric

Cat. No.

Click to enlarge - 140U-L-TL6C1_r_bw

Terminal Lugs

Aluminum

Cu/Al

(1) 500…750 MCM

(1) 240…380 mm2

140U-L-TL6A1

140U-L-TL6A14

Copper

Cu only

(1) 500…750 MCM

(1) 240…380 mm2

140U-L-TL6C1

140U-L-TL6C14

Click to enlarge - 140U-L-TL6A2_r_bw

Aluminum

Cu/Al

(2) 2…500 MCM

(2) 35…240 mm2

140U-L-TL6A2

140U-L-TL6A24

Copper

Cu only

(2) 2…500 MCM

(2) 35…240 mm2

140U-L-TL6C2

140U-L-TL6C24

Click to enlarge - 140U-L-TL6C1_r_bw

Aluminum

Cu/Al

(1) 2…500 MCM

(1) 35…240 mm2

140U-L-TL4A1

Copper

Cu only

140U-L-TL4C1

 2.Kích thước:

Click to enlarge - l-frame_4p_3p

  Chọn các mã sản phẩm khác của MCCB Allen-Bradley

Mã: Bulletin 140UE L-Frame Danh mục: